Wire Ampacity Calculator

Find a conductor’s derated ampacity. WireCoder starts from NEC Table 310.16, applies the ambient temperature correction (310.15(B)(1)) and the adjustment for more than three current-carrying conductors (310.15(C)(1)).

How it works

Derated ampacity = base ampacity (Table 310.16) × temperature correction factor × bundling adjustment factor. Each factor is shown so you can check the work.

Frequently asked questions

Does it include temperature correction?

Yes — full Table 310.15(B)(1) ambient correction by insulation rating (60/75/90°C).

What about more than 3 conductors?

The 310.15(C)(1) adjustment is applied automatically (80% for 4–6, 70% for 7–9, and so on).